Tianjincenterenergy
Tianjincenterenergy-savingrenovationprojectplanandassessmentofenergy-savingeffect
Attheendof2010,TianjincenterdecidedtodeclareLEED-GreenBuildingcertification.Fromtheendoflastyeartoearlythisyear,WiththespecifichelpofCertifiedConsultingfirm,wedevelopedaseriesofenergy-savingprojects.someprojectshasbeenimplementedandhasachievedgoodresults;someprojectshavebeenapprovedbyHainanAirlinesGroupandispreparingimplementation;assessmentofsomeprojectshavebeencompleted,theprojectisenteringthelatestagesofpreparation;someoftheitemsbeingevaluated.
Theseprojectsareasfollows:
1.LightingtransformationprojectofthewalkwayofpublicareasofTianjinCenterapartmenttower
Thecontentoftheprojectistoreplacetheoriginal50Wincandescentlightingofpublicareaswithanewtypeoflighting-LEDbulbs.Althoughprojectimplementationissimple,theeffectishuge.Foreachsetoflamps,theoriginal50Wincandescentlampcupisreplacedwith5WLEDbulb.Bythiswecandoubleextendlamplife,reducethecostofreplacementbulbsandsavealotofpowerconsumption.Fromthebeginningofthisyear,webeginthereplacementwork.Nowthe2,000unitsof2,200setsoflightshasbeenreplaced,inotherwords91%oftheoverallworkhasbeencompleted.Becausethecorridorlightingformorethan12hoursaday,evenifthedeductionofinputcosts,Thataloneannualsavingsinelectricityarealso30million¥.Consideringthefuturereductioninthecostofreplacementbulbs(LEDbulbshavealonglife),theannualcostsavingswillbemore.
Thisworkcanextendtothehallwayoftheoffice.Incandescentlightingofthehallwayoftheofficeachieveto800,now200hasbeenreplaced.Allofthisworkiscompleted,theannualsavingscostwillreach11million¥.
Note:
seeAnnex1.
2.TianjinCentreofficeairconditioningsysteminstallationlayeredelectriccontrolvalve.
TianjinCentreofficebuildingareaisthirtythousandsquaremeters(30,018.13squaremeters),andofficefloorsisupto23layersbelongtohigh-gradeofficebuildingsinTianjin.
IntheconstructionoftheTianjinCenteroftheoriginalownersofthecenterofTianjin(ShanghaiForteLandGroup),eachofficeisindependentofthefancoilairconditioningandrefrigerantpipesforthefancoilisasingle-looppipe(twotubeonegetoneback,inthesummerforchilledwater,inthewinterforheatingwater).Manualvalveisinstalledontheeachlayerofrefrigerantpipe.
Now,officeforleaseandoccupancyrateismorethan80%.Mostoftheofficeisassignedtounitsofpureofficeproperties,butthereareafewtenants,schoolsandotherunits.Becausetheunitsareassignedtothedifferentpropertiesofworktime,itresultindifferentworktime.Forofficeproperties,theworkinghoursisfrom8:
00AMto6:
00PMtimeperiod,butforthepropertiesofschoolsandothertenants,theeveningsandweekendsisalsothenormalworkinghours.
Electriccontrolvalveisproposedtoinstalloneachcircuitpipeoftherefrigerantandelectriccontrolvalveisfocusedandleadedtothecontrolroomofthepropertycompany.
Ontheweekend(ornight)inthecontrolroom,forthemajorityofnoworktime,vacationfloor.wecanturnofftheair-conditioningrefrigerantpipesandonlyopenair-conditioningductsforworkovertimeornormalworkoftheunitfloortosaveenergy(eachfloorsetupamanualvalve,however,atnightonlyafewstaffscarrytheladderandclimbeachflooroftheceilingtoturnoffnoworktime,vacationfloor.thenextmorningtoopen,soitisunrealistic.manualvalveisonlyusedforfloormaintenanceofairconditioninguse).
Foreachofthemainsupplyandreturnpiping,onlyanelectricwatervalveisinstalledonreturnpiping,butitplayaroleofopenorcloseairconditioningrefrigerantofthewholelayer.
Beforenotransformation,Duetodifferentworkinghours,inordertoprovidecoolingandheatingforasmallnumberofeveningandweekendworkunits,wehavetoprovidecoolingandheatingfortheentireofficefloor.
Aftercompletionofthetransformation,inadditiontoafixedscheduleofunitsandintheeveningat18:
00thedayafteranapplicationforcontinuedcoolingorheatingunits,wecancloseallotherfloorsofair-conditioningmediachannels.
Theapplicationdelaycoolingorheatingunits,air-conditioningfeesarecharged.
Accordingtoestimate,theannualcostsavingsis396,000¥.Only150daysinsummercoolingperiod,theannualsavingsis292,500¥.Inwinterheatingperiodalsocansave103,500¥.Sowecanrecovertheseinvestmentwithinayear.
ThisworkhasbeenapprovedbyHainanAirlinesTourismGroupandisreadyforimplementation.
Note:
theenergycalculation,seeannexI
3.frequencycontrolisinstalledonairconditioningsystemtoachieveenergysavingpurposes.
TianjinCentralairconditioningsystemsrefrigerationandcoolingwaterusethetraditionalfixedflowcontrolandcoolingtowerfansusefixedairvolumecontrol,soitmeansenergysavingispotential.
Buildingcoolingsystemisdesignedtoensurethebuildingalsocanoperateintheextremeweatherconditions,takingintoaccounttheuncertaintiesandthereducedcoolingsystemefficiency,sothedesignhasasafetymargin.Thismeansinmostcases,coolingsystemisnotworkinginfullloadcondition.
Particularly24-hourcontinuousoperationofrefrigerationsystems,morningandeveningandnightloadisdifferencesfromdayandnoon.thephenomenon'Marabigcar'willappearwhencoolingsystemloadofadistrictinbuildingislessthanasinglecoolingunitofthesystempeakload.thegreaterthetemperaturedifferencebetweendayandnight,thephenomenonwillbemoreserious.
WemuststartthesecondcoolingunitWhenasinglecoolingunitofthesystemcannotmeettheneedsofaregioninbuilding.iftwounitshavetorunwhenthecoolingcapacityissurplus,thephenomenon'Marabigcar'alsowillappear.Morethantwocoolingunitssimilarly
Basedontheaboveanalysis,duringmostofthetimeofoperationtherefrigerationunitareinnon-full-loadrunning.theindoorunitloadratewiththechangesofoutdoortemperature,butthesystemflowandairflowkeeprunningatfullcapacity,sothishascausedalotofenergywaste.
Foreachrefrigerationunit,thelightertheload,thelowertheefficiencyofthesystem,beforeandafteroutofseasonthisphenomenonwasparticularlyserious.
Forhigh-gradeapartments,hotels,officebuildings,beforeandafteroutofseasoncoolingsystemisonlyusedbyafewusers,butwecannotstoptherefrigerationsystem.Inthisperiodoftime,theoperationoftherefrigerationsystemisnoteconomical.
Thewaterflowandairflowisdesignedonfullload,butfrozenpump,coolingpump,coolingtowerfanisnotnecessarytorunfullspeedwhenrefrigerationunitisrunningatlightload,itcausethewaste.Thisconsumptionisthedominantpartoftheconsumption,whichcanbecomputedorcountedonactualpowerconsumptionorcomparedtosimilarvalues,butitwillbringalotmoreinaccuratestatisticsofthehiddenconsumptionwhenthewaterpumpandfanareirrationalruns.specificallyasfollows:
A-frozensideoftherefrigerationsystem
Tianjincenterthefrozensideofcoolingsystemisdesignedontheconstantflow,asusers’demandchangeswiththechangesofindoorandoutdoortemperature,thismeansthefixedtemperaturerefrigerantflowrequirementsareconstantlychanging.whentheuserdemanddecrease,duetochilledwatersupplyexceedsdemand,watermainchannelsystem,whichwillcausethesystemtoincreasewaterpressure,andaffectthecoolingsystemstability.Inordertostabilizethepressuretoensureconstantflowofchilledwater,thebalancevalveisinstalledbetweenwaterdistributorandwatercollectorinthefreezersideofthecoolingsystem.
Thebalancevalvemoderatelyopen,sothatpartofthechilledwaterdirectlygobacktotherefrigerationunitwhentheuserdemanddecrease.
Balancevalvesettingssolvethesystemrunningstableandconstantproblem,butitwasteofalotofvaluableenergy.
Whenthebalancevalveopens,thechilledwaterflowthroughthevalvedirectlybacktothechilledwatercoolingunitsanddonotparticipateinthebuildingtemperaturecontrol.Butitisuselessthatchilledwaterpumppromotethispartofchilledwater.
Moreover,thispartofuselessworkeventuallyconverteintoheatbytheresistanceeffectofthewaterpipelineandoffsettheequivalentcoldproducedbyrefrigerationunitconsumptionofelectricity.
Ifthechilledwaterpumpsusevariablefrequencycontrol,youcanupgradetheoriginalconstantflowcontrolforthevariableflowcontrol.Forchilledwater,howmuchtheuserdemand,howmanypumpsprovide.Thesystemoperatingpressurecanbeadjustedbychangingthepumpspeedtoachieve.
Slowrunningpump,motorcurrentwilldroprapidly,whilethecirculationpumpmotorpowerconsumptionisproportionaltothesquareofthecurrentwork,whichmagnifytheeffectofenergysavingandavoidtheuselessworktransformingtheheatload.Thetotalenergy-savingisconsiderable,whichisthemainreasonforusingtheconverterindevelopedcountries.
B-coolingsideoftherefrigerationsystem
Tianjincentercoolingunitofcoolingsystemusetoincreaseordecreasethenumberofcoolingwaterpumpstocontrolcoolingwaterflow.
Thecoolingeffectwillbeworsewhentherefrigerationsystemcoolingwaterflowistoosmall,whichwilldirectlyaffecttheunit'scoolingeffect,soitmustrunanothercoolingwaterpump,whichwillcausethecoolingwaterflowofthesystemi